#659001CB1 Circuit Breaker 1.928 inches center to center distance between terminals parallel to length

659001CB1

Circuit Breaker

NSN 5925-00-024-0864

DEMIL
Shelf Life
UOM
NIIN
Demil:
NO
Shelf Life:
N/A
UOM:
1 EA
NIIN:
000240864
Description

Multipole-multiple actuator type body style, 2.490 inches body length, 2.240 inches body width, plastic case material, 1.928 inches center to center distance between terminals parallel to length.

Detail Specifications

Body Style:
Multipole-multiple actuator type
Body Length:
Between 2.490 inches and 2.510 inches
Body Width:
Between 2.240 inches and 2.260 inches
Case Material:
Plastic
Center To Center Distance Between Terminals Parallel To Length:
Between 1.928 inches and 1.948 inches
Center To Center Distance Between Terminals Parallel To Width:
Between 0.740 inches and 0.760 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length:
Between 2.052 inches and 2.072 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width:
Between 0.740 inches and 0.760 inches
Fragility Factor:
Moderately rugged
Boss Height:
Between 0.130 inches and 0.150 inches
Mounting Surface To Terminal End Distance:
Between 2.461 inches and 2.481 inches
Pole Quantity:
3
Arc Quenching Method:
Magnetic blowout
Mounting Facility Type And Quantity:
6 threaded hole
Storage Type:
General purpose warehouse
Special Handling Feature:
Magnetic
Thready Qty Per Inch (tpi):
32
Maximum Continuous Load Current Rating Per Pole:
3.5 amperes ac first location
Maximum Continuous Load Current Rating Per Pole:
3.5 amperes ac second location
Maximum Continuous Load Current Rating Per Pole:
500.0 milliamperes ac third location
Operating Voltage Type And Rating Per Pole In Volts:
250.0 ac all locations
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps:
1000.0 ac all locations
Circuit Protection Type:
Overcurrent all locations
Trip Release Method:
Magnetic-hydraulic all locations
Trip Release Characteristic:
Time delay all locations
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
125.0 all locations
Reset Method:
Manual
Main Contact Tripping Mechanism Type:
Trip free
Manual Actuator Type And Quantity:
3 toggle
Actuator Function:
Trip-reset
Actuator Position Designation:
At each pole
External Actuator Linkage Arrangement:
One, two, and three linked
Internal Trip Release Configuration:
Series trip first location
Internal Trip Release Configuration:
Relay trip third location
Internal Trip Release Configuration:
Series trip second location
Thread Size:
0.138 inches
Trip Delay Time In Seconds Per Rated Continuous Current:
0.300 at 200 pct all locations and 1.000 at 200 pct all locations
Inclosure Protection Type For Which Designed:
Fungus resistant and moisture resistant
Frequency In Hertz:
60.0 all locations
Unpackaged Unit Weight:
14.000 ounces
Thread Series Designator:
Unc
Terminal Type And Quantity:
8 threaded stud
NSN:
5925-00-024-0864
Item Name:
Breaker,circuit
Cage Code:
05234

Manufacturer Part Numbers

Part Number
Cage
RNCC
RNVC
RNAAC
Status
MSDS
SADC
Part Number:
72-317-1NG6
Cage Code:
74193
RNCC:
C
RNVC:
1
RNAAC:
ZZ
Status:
A
MSDS:
SADC:
AC
Part Number:
651322
Cage Code:
05234
RNCC:
5
RNVC:
2
RNAAC:
TA
Status:
A
MSDS:
SADC:
Part Number:
72-317-1MG6
Cage Code:
74193
RNCC:
5
RNVC:
9
RNAAC:
TA
Status:
A
MSDS:
SADC:

  We Guarantee with Every Order

  •   100% Genuine Manufacturers Parts
  •   Every Product thoroughly Inspected
  •   Sales Record Retention of 7 years
  •   Fast Delivery
  •   HAZMAT Certified
  •   Global Shipping

Pricing & Availability

Submit this form for current pricing and availability quote on part number 659001cb1 and/or cross reference parts.
Part / NSN:
Qty:
Your Email:
Phone:
Ref. / PO #:
Company:

We do not share or sell your information to anyone.
Privacy | Terms

Catalog Drilldown
--- Electrical And Electronic Equipment Components
------ Circuit Breakers
--------- Circuit Breakers
------------ P/N 659001CB1

New Products Recently updated in circuit breakers

  • 27-10388-1 circuit breaker
    NSN 5925-00-166-3440

    Multipole-single actuator type body style, 0.250 inches bushing length, 1.312 inches body length, 2.140 inches body width, 2.156 inches body height

  • 1536-007-10 circuit breaker
    NSN 5925-00-166-3440

    Multipole-single actuator type body style, 0.250 inches bushing length, 1.312 inches body length, 2.140 inches body width, 2.156 inches body height

  • 314C920G21 circuit breaker
    NSN 5925-00-165-8693

    3 pole quantity, 150.0 amperes ac all locations maximum continuous load current rating per pole, 600.0 ac all locations operating voltage type and rating per pole in volts

  • KA3150 circuit breaker
    NSN 5925-00-165-8693

    3 pole quantity, 150.0 amperes ac all locations maximum continuous load current rating per pole, 600.0 ac all locations operating voltage type and rating per pole in volts

  • 504C336G21 circuit breaker
    NSN 5925-00-165-8693

    3 pole quantity, 150.0 amperes ac all locations maximum continuous load current rating per pole, 600.0 ac all locations operating voltage type and rating per pole in volts

  • BAB1015 circuit breaker
    NSN 5925-00-165-8694

    1 pole quantity, 15.0 amperes ac single location maximum continuous load current rating per pole, 240.0 ac single location operating voltage type and rating per pole in volts


Best-Selling Products A collection of our most popular products

Last Updated: 12/25/2024