Primary power input shall be 120/208 vac plus or minus 20 percent, 57 to 63 hertz, 3 phase 4-wire wye; output shall be 120/208 vac plus or minus 5 percent at 60 hertz and shall not change more than 1.8 percent per hertz between 57-63 hertz, 50 kva , power factor 0.8 lagging to 0.95 leading, 3 phase 4-wire wye; the product efficiency shall be a of 93 percent at rated load; weight shall not exceed 3000 pounds; operating temperature minus 40 degrees c to plus 71 degrees c; operating altitude minus 100 to plus 7500 feet; depth 29.900 inches; width 50.000 inches; high 40.000 inches
NSN 6610-01-288-2339
NSN 6240-01-072-1097
NSN 5935-00-766-8080
NSN 5855-00-327-2112
NSN 5925-00-269-2685
NSN 5990-00-052-9839
NSN 5920-01-209-2219
NSN 5990-00-752-2126
NSN 5998-00-733-0015
NSN 5905-00-915-1419
NSN 7035-00-079-7189
NSN 6150-00-896-0037