Aluminum; rqmts: airflow: 1270 standard cfm; velocity: 485 fpm; i/p air conditioner: 91.5 degrees f dry bulb, 60.6 degrees f wet bulb; o/p air conditioner: 61.5 degrees f dry bulb, 48.5 degrees f wet bulb; air pressure drop (dry coil)0.34 in.Water max, (wet coil)0.53 in water max; refrigerant: r22; refrigerant pressure drop: 13.2 psi max; evaporator temp: 49.5 degrees f(saturated); condensing temp: 154.5 degrees f (saturated) ; superheat leaving evaporator coil: 10 degrees f; condenser coil sub-cooling: 10 degrees f;
A unit consisting of parallel tubes joined together by a header on headers, utilizing fins to increase the surface area. Designed to be used in conjunction with a duct in which a blower or fan is provided to circulate air through the unit to perform the function of cooling, heating , ventilating and/or dehumidifying (hvac).
Classification: Air conditioning evaporator coils
NSN 6220-01-297-8307
NSN 6620-00-451-1460
NSN 6150-00-614-9568
NSN 2925-01-330-2988
NSN 6620-00-364-6890
NSN 6620-01-431-9176
NSN 5999-01-384-1312
NSN 7035-01-145-5059
NSN 5996-00-143-9377
NSN 5999-01-061-2924
NSN 5990-01-395-4194
NSN 2925-01-068-3844