Plug-in, 2 wire, multi-sensor detector, photoelectric (for smoke) and thermal sensing units; compatible with mxl family of control panels; electrically compatible with existing mxl detector accessories; requires p/n 500-095687, model db-11c (mounting base, series 11) for some older mxl systems; dust resistant; field cleanable photo chamber; solid state, non-mechanical thermal sensor; micro processor based electronics; model fpi-32 programmer/tester (not included) used to electronically program and verify detectors address; fpi-32 allows user to change device from fp-11c to older detector id without having to reprogram control panel; multi-color led flashes green for normal condition, amber for detector fault, and red, when instructed by panel, for alarm condition; capable of bi-directional communication with control panel; current requires 0.750 amps; plus 32 to plus 100 deg. F operating temp; 0 to 93 percent humidity non-condensing; ulc listed
A device designed to detect the presence of predetermined amounts of smoke, dust, and the like, within the measuring area. The presence of any of these substances causes a change in the output signal of the device, which relays a warning message back to a central panel. The device itself does not provide any audible or visible output, or analyze chemical content. Excludes alarm, smoke, automatic.
Classification: Parts of electric sound or visual signaling apparatus other than printed circuit assemblies, nesoi
NSN 5930-01-348-4856
NSN 5930-00-264-3504
NSN 6610-00-314-2605
NSN 5915-01-493-5957
NSN 6220-00-042-3936
NSN 7035-00-093-5840
NSN 2925-00-284-1534
NSN 6150-01-179-7036
NSN 5895-01-463-1940
NSN 6240-01-014-5598
NSN 5835-00-941-4959
NSN 6220-01-339-0067